6 Watertight Floor and Wall Coverings and Paint Systems
This section discusses how watertight floor and wall coverings and paint systems are installed. In this section, the term covering is used for both walls and floors.
Watertight floor and wall coverings and paint systems are designed to protect underlying building parts against moisture (see Section 2.2.2, Watertightness).
Table 3 in Section 3.1.4 and Tables 6 and 7 in Section 4.1.2 provide an overview of where watertight floor and wall coverings and paint systems are required on floors and walls, respectively.
6.1 Types of Wall Coverings
A construction can be waterproofed with:
A watertight tile setting and covering system (i.e., a waterproofing membrane, perhaps applied in liquid form, protected against mechanical impact from tiles or other ready-made surface covering)
A watertight covering (e.g., a PVC covering with watertight joints)
A wet room paint system (i.e., a total system of paint products, such as primer, adhesive, fibre-glass fabric, and paint, which together form a watertight surface)
Manufacturer’s instructions must always be observed (e.g., when making joints and penetrations). Materials from various manufacturers or systems must not be combined, as no documentation exists to validate the efficacy of such combinations.
6.2 Watertight Membranes and Covering Systems
6.2.1 Build-up
Watertight tile setting system is the term used for waterproofing kits,
typically consisting of:
primer, waterproofing membrane with recommended waterproofing tape, sleeves, tile adhesive, tiles, tiling grout, and possibly sealant
a prefabricated waterproofing membrane with ancillary adhesive and other accessory materials
The tile covering is meant to protect the watertight membrane against mechanical load.
Watertight tile setting systems for use on organic substrates, stud walls, and other elements, must meet the specific criteria for achieving an ETA or MK approval (see Annex E. Marking and Approvals). These requirements include water impermeability, water-vapour impermeability, adhesion, layer cohesion, and resistance to shocks and blows, for example. The requirements for watertight tile setting systems are specified in MK 7.00/012, Vægbeklædninger til vådrum. MK prøvnings- og godkendelsesbetingelser (Wall Coverings for Wet Rooms. MK Testing and Approval Conditions) (ETA-Danmark, 2014b).

Figure 75. An example of typical work processes for stud wall and floor used as substrate for a watertight tile setting system where the membrane is applied in liquid form. Floor and wall surface areas must be stable, clean, and sufficiently strong to hold the subsequent waterproofing membrane and tile covering. All sheet joints on the walls and transitions between floor and walls are sealed with mesh reinforcement. Sleeves are fitted (depending on the system) around floor outlets and pipe penetrations. Finally, the waterproofing membrane is applied, and the tiles are mounted.
The substrate is normally prepared by flashing corner joints, connections, floor-wall transitions, pipe penetrations, reinforcing them with reinforcement mesh or special sealing tape and sealing collars.
6.2.2 Tiling
Currently, tile adhesive is almost always used for tiling floors and walls, but it is still acceptable to use mortar. However, mortar cannot be used with approved tile setting systems, all of which require the use of tile adhesive.
Floor-tiling is normally performed on a substrate incorporating the correct falls towards the outlet, as only modest adjustments to falls are feasible with tile adhesive. Falls can be constructed in the substrate in various ways, depending on the specific conditions (see Section 3, Floor Constructions).
The following requirements apply when mounting or laying tiles:
Surface areas must be clean and dust-free.
Tile adhesive is applied in the quantity specified by the manufacturer. The quantity depends on the type of tile, including the geometry of its reverse side, which can be smooth or embossed.
The tile adhesive must be applied so that it covers the entire surface area. The tile adhesive is normally applied using a notched trowel to adjust the amount of adhesive required.
The tiles are mounted so that the whole of its reverse side is covered (e.g., by ’twisting’ the tile into position). Now and again, a tile should be ’slaughtered’ to check that its reverse side is totally covered with adhesive.
If tiles are big, it may be necessary to use adhesive on both the substrate and tile to ensure full adhesive coverage.
Adaptations will normally have to be made to tiles by cutting them. It will usually look best if cut tiles at the perimeter are uniform and not too small. It is a good idea, therefore, to mount the tiles from the centre of the room, so that the width of the cut tiles is uniform on both sides. When testing a layout, ensure that all tiles that need cutting are bigger than half a tile (see Figure 76). There may be other reasons, such as adaptations around doors and windows, which dictate that the tiles be laid differently. In this case, tiles may also be cut to fit around windows or doors.
Figure 76. Laying tiles. Tiles should be cut to a size bigger than half a tile. If laying them from the centre of the room does not always result in tiles being > ½ tile, if necessary stagger the tiles by a ½ tile relative to the centre of the room.
If the format for wall and floor tiles is identical, the joints should line up in the transitions as far as possible.
It is difficult to lay large tiles completely evenly. This is because small irregularities, such as curvature in the tile, thickness tolerances, and minor distortions in tiles when laying them will result in substantial unevenness at tile edges. Furthermore, it is difficult to construct falls towards traditional floor outlets. For these reasons, tiles should be no bigger than approx. 200 × 200 mm, unless they are laid with tapered falls (i.e., laid along the fall lines). Alternatively, trench or corner outlets can be installed in which case the floor area can be made plane but with an overall incline towards the floor outlet.
Although every effort is made to lay the tiles such that they are fully covered with adhesive, so-called ‘drummy’ tiles may appear. These are tiles with a partially hollow space underneath them. Drummy tiles have no bearing on watertightness, since it is not the tiles that make the floor watertight. However, the tiles must stick.
The thickness of floor tiles should be min. 5 mm. The water absorption of tiles should be max. 10 % according to DS/EN ISO 10545-3:1997 (Danish Standards, 1997). Hard-fired tiles with max. 6 % water absorption are used for floors with underfloor heating.
Further information on tiles is available in the publications Fliser på gulv og vægge (Tiles on Floors and Walls) (Brandt, 2006), Fliser og klinker (Tiles and Clinker Bricks) (Hansen, Andreasen & Hansen, 2009), and the BYG-ERFA info sheets Fliser på vægge og gulv – underlag, fliseklæber og fliser (Tiles on Walls and Floors – Substrates, Adhesives, and Tiles), (42) 05 04 11, Misfarvning af fuger i vådrum – årsager, forebyggelse og udbedring (Discolouring in Wet Rooms – Causes, Prevention, and Repair), and (43) 01 03 01, Keramiske fliser og klinker – lægning af gulve i cementmørtel (Ceramic Tiles and Clinker Bricks – Laying Floors in Cement Mortar) (Byg- Erfa, 2014; 2011; 2001).
6.2.3 Tile Coverings in Wet Zones
On stud walls and floor and wall constructions containing organic materials in the wet zone, tile setting systems with an ETA or MK approval for use with the material in question must be used (see Table 3 in Section 3.1.4 and Table 6 in Section 4.1.2.).
The tile setting system must have a proper watertight layer in the form of a membrane. Membranes applied in liquid form must have a thickness of min. 1.0 mm. Prefabricated membranes could be thinner than 1.0 mm, but must be sufficiently robust to resist minor shocks and blows during the construction process. Those primers, waterproofing tapes, collars, waterproofing membranes, adhesives, tile adhesives, tile grouts, etc., specified by the chosen watertight tile setting system must be used because the approval applies to the system. The quantity of materials, curing times, etc., specified in the approval must be adhered to. This means that the liquid membranes must be applied in the correct quantity to obtain the required layer thickness of 1.0 mm (in dry conditions). The approval of the tile setting system applies solely to the substrates mentioned in the approval.
6.2.4 Tile Coverings in Humid Zones
In the humid zone, it is possible to use all the tiling systems approved for use in wet zones. Furthermore, other systems may be used (e.g., systems where the primer and adhesive together provide the wall’s watertight layer without an actual membrane, as such).
Tile setting systems for use in humid zones might have an ETA or MK approval (e.g., a system with a thinner membrane or completely without a membrane), but such an approval is not a requirement. However, manufacturers must always be able to document that the product meets the standards required for obtaining an approval (see MK 7.00/012, Vægbeklædninger til vådrum. MK prøvnings- og godkendelsesbetingelser (Wall Coverings for Wet Rooms. Conditions for MK Tests and Approvals) (ETA-Danmark, 2014b)).
A tile setting system without an approval can only be used on stud walls with a substrate of wet room plasterboard, fibre plasterboard, or calcium silicate sheets mounted either as outlined in Section 4, Walls, or on walls constructed according to a separate ETA or MK approval.
The primers, tile adhesives, tile grouts, etc., specified for the system in question must be used. The same is true of the quantities of material and curing times, etc., stated in the mounting instructions or the approval.
Figure 77. An example of a joint between a stud wall (with two layers of sheets with a watertight approved tile setting system with a membrane) and a plywood subfloor (with PVC floor covering). The wall waterproofing membrane overlaps the upturned PVC floor covering by 50 mm. Filler is applied to the wall above the upturned floor covering to achieve an even transition and the covering is primed. Above the filling and in the flashing, a mesh strip has been fitted to achieve good adhesion between the tile setting system’s waterproofing membrane and the floor covering. The tile covering finishes 100 mm above the floor to protect the tile edge against splashback, shocks, and blows.
Figure 78. An example of a joint between a stud wall (with two layers of sheets with a watertight approved tile setting system with a membrane) and a plywood subfloor (with prefabricated waterproofing membrane). The wall waterproofing membrane overlaps the prefabricated floor waterproofing membrane by 50 mm. The floor membrane finishes 100 mm above finished floor level. Filler is applied to the wall above the upturned tanking membrane to achieve an even transition. Above the filling and in the flashing, mesh sealing tape has been fitted to achieve good adhesion between the tile setting system’s tanking membrane and the floor tanking membrane. The floor tiles are bonded to the screed. A flexible mortar joint has been made in the transition between floor and walls.
Figure 79. An example of a joint between a stud wall (with two layers of sheets) and a plywood floor. Both floor and walls are waterproofed with an approved tile setting tiling system with a waterproofing membrane. A liquid sealant with a mesh reinforcement strip is applied to the joint between floor and walls as shown in the specific laying instructions. The tile setting system’s waterproofing membrane covers all wall areas and the whole floor area. The thickness of the membrane layer is min. 1.0 mm throughout. The falls in the floor are incorporated in the subfloor. A flexible mortar joint has been applied in the transition between floor and walls.
6.3 PVC Coverings
6.3.1 Prerequisites for Using PVC
PVC floor and wall coverings (subsequently called PVC coverings) are intrinsically watertight if the correct materials are used, and the work is carried out correctly. PVC coverings for use in wet rooms must be roll material which is homogenous, or laminates of homogenous layers. They must meet the quality requirements in Table 10 and must contain max. 50 % filler in each layer for reasons of weldability.
PVC coverings meeting DS/EN ISO 10581 (Danish Standards, 2013), contain max 45 % filling material and thus meet the requirements for filling material content.
Nowhere may the coverings be thinner than 2.0 mm for floors and 1.5 mm for walls. For reasons of adhesion, they must have a planar reverse side.
Figure 80. Welding joints in resilient floor coverings. Welding joints are made at inward as well as outward corners with oblique sections made in the upturned floor covering. For pipe penetrations, the joint is offset, so that wire-welding of the joint will not be hampered by the penetration. The spacing between pipe and wall must be min. 30 mm and the penetration must be made using a watertight collar bush designed for PVC coverings.
Pipe penetrations are made watertight with collar bushes. For cast-iron discharge pipes as well as renovation tasks where pipes cannot be moved, watertight collars welded to the floor covering are used. If using PVC, the following criteria must be met:
No joints are permitted above sheet end joints in floors or walls.
All sheet joints must be surface-ground and then primed to reduce absorbency.
The covering must be fully bonded to the floor and/or walls.
The floor and/or walls must be fully covered.
All joints in the covering must be wire-welded.
The number of joints and pipe penetrations in the covering should be kept to a minimum.
The PVC wall covering can be welded to the PVC floor covering in a watertight joint (see Figure 80). Alternatively, an overlap joint can be made.
6.3.2 Checking the Workmanship
Work with PVC coverings should be carried out by professionals holding a welding certificate and the workmanship should be subject to strict control. The certificate documents that they have completed a course and passed a test in working with PVC wet room applications (including the construction of subfloors with falls and wire-welding coverings).
Building owners should demand documentation for the work having been checked during implementation and at the point of hand-over. This should include a final check of all outcome requirements, especially the watertightness of welded joints.
Contractors should be affiliated with an approved, external control scheme, which regularly samples work carried out, such as Gulvbranchens Vådrumskontrol (GVK) (Flooring Sector Wet Room Control). Building owners should request copies of the contractor’s report to the control scheme. The report will document that sample control has been carried out, including testing the watertightness of welded joints.
PVC coverings supplied or installed by firms affiliated to Gulvbranchens Vådrumskontrol (GVK) can be expected to meet the quality requirements listed in Table 10.
Contractors affiliated to the GVK scheme can be expected to have the work carried out by floor fitters with a welding certificate. Furthermore, the work is part of an external quality assurance scheme, implying that the regulatory body will perform regular sampling of the work carried out. Information on Gulvbranchen’s rules for delivery, installation, and external control of PVC coverings in wet rooms is available from
www.gulvbranchen.dk.
Table 10. Quality requirements for PVC roll materials used as floor or wall coverings in wet rooms. The manufacturer must be able to document that the product meets the stipulated requirements and specify which ancillary materials to use with them (e.g., primers, adhesives, welding wire, and sealants).