1.3 How to Interpret Building Regulation Provisions
The following comments relate to Building Regulation provisions. The numbers refer to the respective sections in BR10.
3.3.2 Bath and Toilet Rooms
The provision shall ensure that wet rooms are designed to be accessible to everyone (see Section 1.7, Accessibility and SBi Guidelines 249, Tilgængelige boliger – indretning (Accessible Dwellings –Layout) (Sigbrand & Jensen, 2015)).
4.5 Moisture and Durability
§ 5 (3): The part of the room exposed to water refers to those areas likely to be directly exposed to water (e.g., when showering or cleaning). All floor areas are regarded as exposed to water load. All wall areas less than 2 m away from shower, bathtub, or washbasin are considered exposed to water load (at least occasionally). Note that the area of the wet room exposed to water load is not identical to its wet zone, where regular (often daily) exposure to water is expected. In the entire room, wall areas and pipe penetrations must be sufficiently watertight to prevent moist air from infiltrating moisture-sensitive constructions. In practice, therefore, all walls should be made watertight and should have watertight pipe penetrations.
§ 5 (4): Draining water to a floor gully means that no back slope or depressions (which cause ponding) are permitted anywhere on the floor. Hence floors must be constructed with slopes to avoid the risk of ponding. Ponding is defined as water accumulations extending beyond 250 mm (upper limit) or deeper than 1 mm. If this is unclear, the slope should be tested by pouring water onto the floor and measuring the extent and depth of depressions after 5 minutes. See Hvor går grænsen? (Where’s the Limit?) Murerfaget (Danish Construction Association, 2014) and Fliser på væg og gulv (Floor and Wall Tiles) (Brandt, 2006).
§ 5 (5): Floor areas expected to be regularly exposed to water are those around the shower stall, bathtub, and floor gully (see Figures 1–11).
§ 5 (6): Waterproofing systems are considered suitable if they are included in these Guidelines or have received an approval adapted to national Danish provisions (e.g., an MK approval or an ETA (European Technical Assessment)) (see Annex E. Marking and Approvals).
6.3.1.2 Residential Buildings
A distinction is made between single-family houses where natural ventilation can be used and other buildings where mechanical ventilation is a requirement.
In single-family houses with natural ventilation, openings for fresh-air supply and extraction of humid indoor air must, be sized as specified in the explanatory text in the Building Regulations.
In other buildings such as multistorey buildings, demand- or moisture-controlled ventilation can be used. In buildings with several wet rooms, the upshot of this rule is that normally individual extraction can be controlled for each room or extraction can be controlled by the wet room with the highest humidity.
1.4 When do Building Regulation Provisions Apply?
Building Regulations and hence the provisions for wet rooms apply to both new buildings and to significant conversions or extensions. Minor alterations, such as replacing tiles in existing wet rooms, are exempt.
Situations may occur (e.g., geometric limitations, old timber joist constructions, and existing board partitions) which require special attention (see Section 2.3, Constructing Bathrooms in Old Houses).
When renovating existing bathrooms, constructions that were legitimate at the time of construction may remain in use. However, some old constructions such as painted slag plate walls are not as watertight as more recent wall types, including concrete walls or walls fitted with waterproofing membranes. The watertightness of such constructions should therefore be improved when renovating (e.g., by fitting a waterproofing membrane) particularly as contemporary water loads tend to be heavier than in the past (see Section 5, Renovating Existing Bathrooms).
Brick or lightweight concrete walls absorb water and should therefore always be fitted with a waterproofing membrane in wet zones (e.g., in and around shower stall and bathtub).
Changes always require vigilance despite initially seeming minor in many cases. For example, replacing PVC flooring with tiles does not always constitute a minor change. This is because tile flooring requires a more rigid substrate, which must be replaced if it fails to meet the requirements in Table 4, Section 3.3.2, Timber Joist Constructions and Subfloors. Furthermore, replacing PVC flooring with tiles would normally require the gully to be replaced as well (see Section 3.3.5, Floor Gullies and Plumbing Installations).
As a rule, installing a new layer of tiles on top of existing wall or floor tiles will is legitimate. Installing a new layer of tiles on an existing floor will normally require the installation of a new gully because the latter is required to be flush with the floor surface (see DS 432, Norm for afløbsinstallationer (Code of practice for Sanitary Drainage - Wastewater Installations) (Danish Standards, 2009b). Existing floor gullies must not be raised using concrete, plastic frames, and other materials listed in Section 8.3, Wastewater Installations.
1.5 Wet-Room Zones
Wet room zones include floors and walls. They do not include ceilings. Provisions for walls in wet rooms only apply when there is a risk of the walls being exposed to water (i.e., in wet rooms with showers).
1.5.1 Wet Zones
The wet zone includes parts of the room regularly – often daily – which are directly exposed to water. These are governed by the strictest requirements for construction, materials, and surface finish.
Wet zones includes:
the whole floor
the bottom 100 mm of all walls
walls near to shower stalls, bathtubs, and washbasins with shower mixer
Shower Stalls
Shower stalls are defined as shower areas, corners, and actual stalls that are walled on three sides. The shower stall or shower area will typically be delimited by a shower curtain, screen, or glass door. A standard shower stall will usually measure 800 × 800 mm or 900 × 900 mm. It can also be circular or have different measurements relative to the surrounding architecture (e.g., 700 × 900 mm, 600 × 1000 mm).
If the shower is located centrally on a long wall, the actual shower area is estimated to extend 450 mm either side of the shower unit while the wet zone extends a further 500 mm either side of the shower unit. This means that the wet zone extends as far as 950 mm either side of the shower unit.
The width of the room will determine whether the wall opposite the shower unit should be included in the shower area (see Figure 1). If the room is narrower than 1.3 m, the opposite wall will form part of the shower area and all walls in the room are treated as part of the wet zone (see Small Wet Rooms).
Figure 1. The shower area or shower stall includes the area around the shower unit. It will typically be delimited by shower walls, screens, shower curtains, or shower doors. If the room is narrower than 1.3 m as shown in the figure, the opposite wall is considered part of the shower area and all walls in the room are considered within the wet zone.
On the walls, the wet zone extends as far as the ceiling. In very high rooms, the area above normal ceiling height (i.e., min. 2.3 m) can be considered a humid zone (See Figure 2 in Section 1.5.2, Humid Zones).
If permanently fixed screens are fitted tightly against the walls, these will delimit the wet zone on the walls (see Figure 3 in Section 1.5.2, Humid Zones). Screens can also be installed as doors when they fit tightly against the wall on which they are hung, and reach approximately floor level (i.e., leaving just enough space for the doors to open and shut).
Utility Rooms, Toilet Rooms, and Washrooms
In utility rooms, toilet rooms, washrooms, and similar areas with floor gullies and walls with no anticipated water exposure, the wet zone includes the floor and the bottom 100 mm of all walls. The remaining wall surfaces are not subject to any requirements.
Small Wet Rooms
In small wet rooms (with a floor area of max. 3.25 m2 or a max. width of 1.3 m in the shower area or stall), the wet zone includes all wall surfaces (see Figure 8 in Section 1.5.2, Humid Zones).
Provisions only apply to the bottom 100 mm of the walls in small utility rooms, toilet rooms, and washrooms with floor gullies where walls are not expected to be exposed to water or high relative humidity.
1.5.2 Humid Zones
The humid zone of a room is the area of wall outside of a wet zone. The walls in the humid zone are exposed to humidity to a greater extent than the rest of the rooms in a house due to high relative humidity and occasional water exposure. For this reason, humid zones are also subject to stringent requirements in terms of materials and construction.

Figure 2. The wet zone and humid zone in a wet room with a shower stall. The wet zone includes the whole floor, the bottom 100 mm of the walls, and the wall area within 500 mm of the shower stall demarcation. On the walls, the wet zone extends as far as the ceiling. In rooms with very high ceilings, the area above normal ceiling height (i.e., min. 2.3 m) can be considered part of the humid zone. Water from the floor must be drained off to a floor gully (i.e., the floor should slope towards the gully). The area delimited by the dotted line shows the positions of slopes in the floor where no pipe penetrations are permitted. This area extends 500 mm from the shower stall demarcation. Given that no ponding or back slope is permitted on the floor, it is advisable to lay the floor with slight slopes towards the gully from all directions. Floor coverings or waterproofing membranes must be sealed to the floor gully with a watertight joint.

Figure 3. The wet zone and humid zone in a wet room with min. 250 mm wide permanently fixed screens around shower stall. Screens can also be installed as doors if the doors reach the floor and fit tightly against the wall on which they are hung. The wet zone includes the whole floor, the bottom 100 mm of the walls, and the walls inside the screens. The wet zone extends up the walls as far as the ceiling. In rooms with very high ceilings, the area above normal ceiling height (i.e., 2.3 m) can be considered part of the humid zone. If the floor in the shower stall is separate from the rest of the floor (e.g., if it is recessed) pipe penetrations are permitted immediately outside the screen. Since no ponding or back slope is permitted on the floor, it is advisable to lay the floor with slight slopes towards the gully from all angles. Kerbs, which demarcate wet areas, should be avoided if possible and must not exceed 25 mm in height. If a kerb is used, it will be necessary to install an extra floor gully outside the shower stall to comply with provisions for floor drainage. Floor coverings or waterproofing membranes must be sealed to the floor gully in a watertight joint.

Figure 4. The wet zone and humid zone in a wet room with a corner bathtub. The wet zone includes the whole floor, the bottom 100 mm of the walls, and the wall area within 500 mm of the bathtub. On the walls, the wet zone extends as far as the ceiling. In rooms with very high ceilings, the area above normal ceiling height (i.e., 2.3 m) can be considered part of the humid zone. No pipe penetrations are permitted within min. 500 mm from the tub (marked by the dotted line in the figure). In floor and wall constructions requiring waterproofing, the watertight layer must be continuous and must not be broken or omitted near bathtubs or permanent fixtures. For example, waterproofing membranes and tiles must be continued under and behind the bathtub. Floor coverings or waterproofing membranes must be sealed to the floor gully in a watertight joint.

Figure 5. The wet zone and humid zone in a wet room with min. 250 mm wide permanently fixed screens around a bathtub. In this case, only the walls inside the screens count as part of the wet zone and pipe penetrations can be made in the floor immediately outside of the screens. Floor and wall constructions requiring waterproofing must have a continuous watertight layer, particularly around bathtubs and permanent fixtures. Therefore, waterproofing membranes and tiles must be continued under and behind bathtubs. Floor coverings or waterproofing membranes must be sealed to the floor gully with a watertight joint. In very tall rooms, the area above normal ceiling height (i.e., 2.3 m) can be considered part of the humid zone.

Figure 6. Walls near washbasins only count as part of the wet zone if the washbasin fixture includes a shower attachment. In this case, the wet zone extends from the floor to 500 mm above the washbasin and 500 mm outward on either side of the basin. If there is a shower attachment, a floor gully must be installed and the floor must slope towards the gully (in the area delimited by the dotted line). Pipe penetrations must be distanced min. 500 mm from the floor gully. If the washbasin shower attachment is the only shower in the wet room, the rules for shower stalls apply (see Figures 2 and 3).

Figure 7. Utility rooms, toilets, and washrooms with floor gullies are considered wet rooms. However, these rooms will usually only be exposed to water on the floor (incl. the bottom 100 mm of the walls), which comprise the wet zone of these rooms. Water from the floor must be drained off to the floor gully (i.e., the floor should slope toward the gully). The sloping should reach 500 mm from the gully and the remaining floor can be laid horizontally. Since no ponding or back sloping is permitted on the floor, it is advisable to lay the floor with slight slopes towards the gully from all angles.

Figure 8. An example of a small wet room (i.e., smaller than 3.25 m2 or max. 1.3 m wide) where the entire room is a wet zone. In this example, the room measures approx. 1.6 × 1.6 m. In such rooms, the shower stall cannot be effectively screened off and should therefore be placed as far from the door and windows as possible, if they are included in the room (e.g., in the corner between the toilet and washbasin as shown). The doors of small rooms should open outwards to ensure that it can be opened when the room is used by persons requiring assistance.

Figure 9. An L-shaped wet room where the shower is placed in the room’s natural recess. If the room size exceeds 3.25 m2, the wall behind the toilet is included in the humid zone as there is no risk of it being splashed with water during showering. The wall with the window will normally also belong in the humid zone. Whether or not the wall is classed as part of the humid zone depends on the distance between the window wall and the opposite wall in the shower stall. If the distance exceeds 1.3 m, the window wall is classed as part of the humid zone. If the distance is less than 1.3 m, it is classed as part of the wet zone.
1.6 Load Classes
The water and moisture exposure in a wet room depends on how often and how long the wet room is used, ventilation efficiency, and airing. A further determinant is whether wet room surface areas and fixtures are exposed to significant variable mechanical loads in addition to water and humidity. Based on the expected load, a distinction is made between the following wet room classes:
For wet rooms classed High with very high levels of water load with ponding on the floor for lengthy periods and/or direct powerful high-pressure washing of surface areas, the degree of exposure must be assessed separately and special measures implemented. Particular attention should be paid to penetrations and joints in the wet room construction. Wet rooms with major water load are typically found in highly exposed rooms within certain parts of the food industry.
During planning, design, and construction, a wet room is classed in the wet room category best describing its future use. When in doubt as to which wet room class to use, select the highest of the relevant classes to achieve an acceptable level of protection against water- and humidity-induced damage.
1.7 Accessibility
In dwellings with more than one bathroom and toilet room, the main bathroom should have the greatest degree of accessibility and at least one toilet room must be located at floor level (according to the 2010 Building Regulations, cf. 3.3.2 (1)) (Ministry of Transport, Building and Housing, 2010).
If possible, bathrooms should be laid out to provide access to self-reliant wheelchair users and should be prepared for adaptation to accommodate disabled persons with further needs. Dwellings under the jurisdiction of the Danish Act on Social Housing must be designed to enable disabled persons to use the shower and toilet.
Figure 10. Example of a bathroom and toilet room of dimensions and design ensuring that wheelchair users can use it. The shower stall is positioned to provide the required distance beside the toilet. Measurements comply with those recommended in SBi Guidelines 249, Tilgængelige boliger – indretning (Accessible Houses – Design) (Sigbrand & Jensen, 2015). The wall with the toilet is a humid zone because the shower will not splash water on this wall (the recess depth is assumed to be min. 250 mm).
To ensure optimal design, bathrooms and toilet rooms should measure min. 1.8 × 2.9 m.
If a bathroom and toilet room is used by a self-reliant wheelchair user, it needs to be big enough for this person to be able to use the toilet and washbasin. Accordingly, there must be a turning area of min. 1.5 × 1.5 m.
For users requiring assistance, the toilet should be placed with a free space of min. 0.9 m from one side of the toilet to the wall and other fixtures, allowing space for a carer. This space is also used to park the wheelchair before the user moves to the toilet. Walls behind the toilet should be dimensioned for installing arm rests capable of supporting the full weight of a person.
In front of the toilet, washbasin, and shower stall, the distance to the opposite wall or fixtures should be min. 1.5 m. Retaining a free space of 1.7 m in front of fixtures will provide optimal conditions for a carer to manoeuvre around and assist a disabled person. These dimensions also cater well to other users, as the depth provides space for furnishings (e.g., 0.6 m deep units, washing machines, and tumble driers).
Shower stalls should be min. 0.9 × 0.9 m and can be constructed with a recess max. 10 mm deep. It is advisable to construct the walls in the shower stall to enable the installation of grab rails.
To ensure sufficient strength, it may be necessary to reinforce stud walls if these are installed.
The floor should be easily cleaned and non-slip in dry and wet conditions.
Doors in bathrooms and toilet rooms should have a free opening of min. 770 mm, but preferably 870 mm. This will enable unhindered access for wheelchair users. Doorsteps should be avoided.
Walls should be constructed to support a ceiling lift.
The shower should be adjustable by a person sitting on a bath seat. Thus, the shower mixer taps should be placed 0.9–1.0 m above floor level. The water temperature should be thermostatically controlled, and the taps should have clearly-marked red and blue symbols.
Further information about designing to meet the needs of persons with physical impairments is available in SBi Guidelines 249, Tilgængelige boliger – indretning (Accessible Houses – Design) (Sigbrand & Jensen, 2015).
1.8 Planning and Control
Measured in square metres, wet rooms are the most expensive rooms in houses, and defective wet rooms can lead to serious secondary damage. Careful planning and control of both design and construction are therefore essential to minimise the risk of error, failure, and damage.
Checklists, or similar systems, should be prepared for use in the design, project review, and construction phases. Checklists should be adapted to the specific project at hand. Annex A. Checklists for Design and Construction details example lists, and what these should contain at minimum.
Currently two statutory orders exist on quality assurance of construction work: Bekendtgørelse om kvalitetssikring af byggearbejder i alment byggeri m.v. og ombygninger efter lov om byfornyelse og udvikling af byer (Statutory Order on Quality Assurance of Construction Work in Social Housing, etc., and Conversions Pursuant to the Law on Urban Renewal and Development) (Ministry of Urban Areas, Housing and Rural Districts (now defunct), 2011)) and Bekendtgørelse om kvalitet, OPP og totaløkonomi i offentligt byggeri (Statutory Order on Quality, PPP, and Overall Financing) (Ministry of Climate, Energy and Utilities, 2013).
If a declaration is made noting that a construction carries risks pursuant to one of the applicable statutory orders on quality assurance, the project checklists must also explain the measures being taken relating to the declaration (for example: rigorous supervision or extra maintenance in connection with the use of the wet room).
1.9 Planning, Design, and Construction
1.9.1 Process
Work to construct a wet room can be divided into different phases; from selecting a load class to usage and maintenance of the new wet room. All phases must be completed correctly to ensure a sound and well-functioning wet room.
Table 2 shows a simple process diagram for wet room construction. The process is described in general terms but can be adapted to more specific constructions and installations as required. The individual items in the diagram are discussed in more detail in Sections 1.9.2 to 1.9.7.
The specific activity is shown in the left column of the diagram. Special focus areas concerning wet room quality are listed in the middle column and remarks on individual activities are listed in the right column.
Table 2. Simple process diagram showing the different phases of wet room construction. The individual items in the diagram are discussed in more detail in Sections 1.9.2 to 1.9.7.