Wall constructions below the double lines are often used in renovation projects. At minimum, all wall types should be levelled and the sheeting installed prior to tiling or installing PVC facing. Alternatively, an additional wall can be erected in front of the old wall (see Section 4.4, Using Existing Interior Walls). Board partition walls and half-timbered walls must only be used if given a sheet covering, which is subsequently waterproofed.
The column applies to tile setting systems without membranes (see definition of tile setting systems in Section 6.1. and paint/wet room paint systems in Section 6.3.)
'Watertight' should be understood as MK-approved panels with an intrinsically watertight surface or surface coating such as a plastic coating.
Laminate sheets include both solid laminate sheets and sheets with a laminate covering.
Adhesion must be documentable.
Tiles can be used. Painting on inorganic substrates should be limited to classes L and M because considerable maintenance must also be anticipated in class H humid zones.
It is feasible to install PVC facing on plastered brick walls to ensure watertightness, but it is difficult/impossible to do this and achieve an aesthetically satisfying result because all irregularities are visible through the covering
4.2 Heavy-Grade Walls
4.2.1 Build-Up
Heavy-grade walls usually consist of concrete slabs, brickwork, or lightweight concrete slabs/blocks. Traditionally, inorganic constructions have been considered intrinsically watertight, which is usually correct for commonly used concrete types whose joints and casting joints are tight. By contrast, once brick or lightweight concrete walls absorb moisture, this moisture is transported to adjacent rooms or building parts (e.g., timber joist constructions). Such walls should therefore always be waterproofed prior to tiling (e.g., using an ETA or MK approved tile setting system).
Preparing Wall Areas
Prior to installing a facing, the wall area must be prepared. All slab joints and wall-to-wall joints must be waterproofed and possibly reinforced. Special care must be taken with joints between new and old walls and between exterior and interior walls. Brick walls must be plastered to get a plane surface area sufficiently strong to support the subsequent facing. Transitions between floor and walls must be flashed to waterproof them min. 100 mm out across the floor and min. 100 mm up the walls measured from finished floor level.
Wall-Covering Materials
Tiles are commonly used as covering for heavy-grade inorganic walls. Watertight PVC facing can also be used but is less common. This is because even tiny irregularities in the surface area will show through the facing.
Tiling
Tiles are installed using flexible tile adhesive so that minor movement from residual shrinkage and moisture and heat exposure is compensated for. If the wall has been waterproofed with a membrane from an approved tile setting system, tiles are fixed as specified in manufacturer's instructions, including using the tile adhesive stipulated in the approved tile setting system.
Formerly, tiles were often fixed directly in cement-lime mortar (corresponding to mortar KC 35/65/650). The method is still applicable for inorganic walls where no waterproofing membrane is used. It is particularly suitable if using tiles of varying thickness or with an uneven reverse side.
The traditional method entails fixing tiles directly to a raw brick wall with a blob of mortar for each tile. This method is no longer applicable in wet rooms. This is because a cavity is left behind the tiles which, in unfortunate circumstances, may cause water to be transported into the brickwork (or other substrate). Furthermore, microorganisms, including mould fungus may develop in these cavities.
Tiled walls are sealed with tile grout. Joints between floor and walls (or other surfaces) can be sealed with flexible grout if only minor movement is anticipated. This is likely to be the case in well-constructed wet rooms where walls and floors are properly joined. Where major movement is expected, acoustic conditions require compensation, or where minor cracks in the sealant is unacceptable for hygienic reasons, resilient sealant such as silicone (for wet room use) is used (see Section 7.1, Joints).
4.2.2 Concrete Walls
Joints must remain watertight. This applies to joints between concrete slabs and between concrete walls and other walls, floors, and ceilings. Waterproofing of joints can be achieved with mesh reinforcement to which a liquid waterproofing membrane is applied. Alternatively, special sealant tape can be used.
Prior to applying a water-repellent surface finish, form coating
or other impurities must be removed to ensure adequate adhesion. Concrete walls which have not cured sufficiently should not be tiled
to any great extent, as shrinkage can be damaging and can cause tiles to crack. The curing time is relative to the concrete composition, thickness, temperature, and moisture conditions. As a rule, a minimum of 2–3 months should elapse from casting the concrete to fitting the tiles.
4.2.3 Lightweight Concrete Walls
Lightweight concrete walls can be made of cellular concrete or lightweight aggregate concrete.
Tiling of lightweight aggregate concrete should not be done until the moisture content has dropped to 4–8 percent by weight, depending on the density. Drying will normally last between 3 weeks and 2 months in a closed-off, heated house, depending on the drying method used. Residual moisture content should be determined prior to starting the tiling process. Information on drying processes and measuring residual moisture content is available from lightweight aggregate concrete manufacturers.
Cellular concrete will normally dry in about 3 weeks in a closed-off house heated to 20 degrees or more.
Since lightweight aggregate concrete shrinks while curing, joints must be designed to remain watertight. This applies to joints between concrete slabs and between lightweight concrete walls and other walls, floors, and ceilings.
Waterproofing of joints can be done by mesh reinforcement to which a liquid waterproofing membrane is applied, or by using special sealant tape.
After drying and before the wall covering is applied, lightweight concrete walls must be prepared (e.g., using a cementitious grout filler). Furthermore, the walls (especially in the wet zone) must be waterproofed prior to fixing the tiles. For example, this can be achieved using an ETA or MK approved watertight tile setting system with a min. 1.0 mm thick waterproofing membrane.
The approval often covers stud-wall applications with sheet cladding. One should ensure that the system is applicable on a substrate of lightweight concrete before using it.
4.2.4 Brick Walls
Inden fliseopsætning skal murede vægge pudses, så de får en jævn, glat overflade. Især i vådzonen bør væggene vandtætnes, før fliserne sættes op. Det kan fx ske ved at anvende et ETA- eller MK-godkendt vandtæt flisesystem med en mindst 1,0 mm tyk vandtætningsmembran. Godkendelsen gælder ofte for brug på skeletvægge med pladebeklædning. Det skal sikres, at systemet kan benyttes på underlag af tegl/puds.
4.3 Stud Walls
4.3.1 Application Area
The application area for stud walls depends on the wall construction (i.e., spacing of studs, how many sheet layers, sheet thickness, and other factors) and on the waterproofing principle used (see Tables 6 and 7 in Section 4.1.2, Combinations of Wall Constructions and Waterproofing Systems). The walls must be watertight from floor to ceiling or at least to standard ceiling height (which is 2.3 m above finished floor level).
Stud walls can be waterproofed using one of the following solutions:
A watertight facing (such as a 1.0 mm waterproofing membrane forming part of an ETAG- or MK-approved tile setting system, or a min. 1.5 mm PVC facing)
A watertight paint system
A watertight layer of foil underneath a moisture-proof sheet or board facing
A watertight facing or paint system must be implemented as described in Section 6, Watertight Floor Coverings, Facing, and Paint Systems.
A watertight layer of foil, installed as part of the wall construction, must be polyethylene foil (PE foil), min. 0.20 mm thick, or another quality foil with a documented long lifespan. The quality of plastic, rubber, or bitumen-based foils can be documented by demanding that the foil meet the requirements for moisture barriers in SPCR 128 (SP, 2004) and SP technique 1380 (SP, 2005).
Foils of recycled plastic cannot always be expected to have a long lifespan.
Only One Watertight Layer – No Vapour Barrier in Exterior Wall
Stud walls in wet rooms must only have one watertight layer. This ensures that water from leakages can escape, avoiding an accumulation of moisture and subsequent damage to the wall. In exterior walls constructed as stud walls, a vapour barrier is normally installed on the warm side of the insulation (e.g., between the stud and the interior facing). In wet rooms with exterior walls constructed as stud walls, the watertight facing or paint will also act as a vapour barrier. To avoid moisture accumulating between the vapour barrier and the wall’s watertight layer, the typical vapour barrier should be omitted (see Figure 56).

Figure 56. In wet rooms, the watertight wall covering also functions as a vapour barrier. Consequently, no further vapour-blocking layers must be installed behind moisture-sensitive sheet facings like gypsum board or wood-based sheets, as this will introduce a risk of moisture accumulation in the material. For exterior walls, this means that the vapour barrier behind sheet facings must be omitted, or that moisture-resistant sheets should be used.
Watertight tile coverings and paint systems can be assumed to meet Building Regulation requirements for moisture protection of exterior stud walls when the facing or paint system has a Z-value of min. 100 GPa s m2/kg. A moisture assessment of the whole wall construction should always be made to ensure that no layers are incorporated into the wall which may cause condensation, such as a tight wind barrier.
However, two watertight layers in a construction can be used if:
it can be ascertained that no moisture will accumulate between the two watertight layers (for example, a watertight PVC covering can be used directly on top of sheeting with a watertight surface).
the material enclosed between the two watertight layers is water-resistant. Water must not penetrate to the underlying construction. For example, calcium silicate sheets can be mounted on a vapour barrier of 0.20 mm PE foil and then receive a watertight tile covering. Sheeting used between two membranes must be resistant to mould
4.3.2 Constructing Stud Walls
Rigidity of Stud Walls
In wet rooms, stud walIs are required to have greater rigidity than stud walls in dry rooms to counteract damaging deformation and failure in watertight layers. Enhanced rigidity can be obtained with less spacing between studs, stronger studs, a double layer of sheets, and increasing sheet thickness. Requirements are dependent on the desired facing or treatment.
Sheets are normally installed on a steel or timber stud. All sheet edges must be supported. Stud walls must be constructed with stud spacing, sheet thickness, and screw spacing as stated in Sections 4.3.3 and 4.3.4.
Reinforcement for Fittings and Penetrations
When installing fixtures and fittings, equipment, and other elements which subject the walls to significant loads, measures must be taken to ensure that the loads are absorbed without the risk of failure occurring in the watertight layer.
A wall-hung toilet or washbasin must be installed on a mounting frame bolted to the floor or subfloor. The mounting frames should be constructed with protruding bolts long enough for the sanitary fixtures to be mounted on the sheet facing after the waterproofing system has been installed.
If special loads are planned (e.g., fitting arm rests), reinforcement must be installed, potentially in the form of securely fixed nogging or steel mounting plates (e.g., fastened between two studs). It might be necessary to erect extra studs for additional reinforcement.
The position of the shower slide bar, fixtures, and other elements, should be planned prior to installing the sheet facing. This helps ensure that reinforcement is added behind the sheets (e.g., nogging or a mounting plate fixed to the studs in the stud).
If load is transmitted to the stud walls from adjacent building parts, this could lead to deformation of the walls with the ultimate risk of leakages in the watertight layers. Connections should therefore be constructed to enable movement to be absorbed without the risk of failure in the watertight layers, coverings, and paint systems. Near the ceiling, special ceiling rails can be used to absorb deflections from the deck, and sealant can be applied between the walls to absorb movement in materials and constructions. Alternatively, the walls can be dimensioned for the loads.
Figure 57. The position of studs and nogging must be planned so that the incorporation of mounting frames (for the toilet and washbasin) and piping (for water supply and discharge) can be run without weakening the stud walls (e.g., due to battens being cut). Mounting frames for wall-hung toilets must be fixed to the deck or subfloor.
4.3.3 Sheets for Watertight Facing
Possible sheet substrates for watertight facing could be:
Table 8 lists inter-related sheet thickness and spacing for studs and screws.
Table 8. An overview of sheet thickness and spacing for studs and screws for stud walls with sheets as substrates for watertight facing.